Chapter 7
Power System Reliability
Nepal Electricity Authority past exam questions
Past questions and answers
1 question set from this chapter. Most repeated first.
- 2082 · 2nd Paper · 10 marks
Discuss the Loss of Load Probability (LOLP) and Expected Energy not Served (EENS) while evaluating reliability of a power system.
Answer
Loss of Load Probability (LOLP) and Expected Energy Not Served (EENS) in Power System Reliability Evaluation
1. Context
Power system reliability evaluation is broadly divided into adequacy (ability to meet demand) and security (ability to withstand disturbances). LOLP and EENS are the two principal probabilistic adequacy indices used in generation planning — they quantify the risk that installed generating capacity will fail to meet the load demand, taking into account random forced outages of generating units.
2. Loss of Load Probability (LOLP)
Definition: LOLP is the probability (or expected proportion of time) that the system's available generation capacity is less than the load demand.
Computation:
- Build the Capacity Outage Probability Table (COPT) for all generating units using their Forced Outage Rate (FOR):
- For a unit of capacity and FOR , the two-state model gives:
- Convolve all units to obtain the probability of each capacity outage state .
- Arrange the daily peak load duration curve (or hourly load model).
- For each period with load :
- Aggregate over the year:
Units: Usually expressed as days/year or as a dimensionless probability.
Interpretation: An LOLP of 0.1 day/year means the system is expected to be short of generation on 0.1 day in a year — the standard planning criterion in many utilities (e.g., 1 day in 10 years).
3. Expected Energy Not Served (EENS)
Definition: EENS (also called Expected Unserved Energy, EUE) is the expected amount of energy (MWh) that cannot be supplied to customers over a given period because of generation inadequacy.
Computation:
where:
- = probability of capacity outage state
- = load in period
- = duration of period (hours)
- The term captures the magnitude of the shortfall, not just its occurrence.
Units: MWh/year (or GWh/year).
4. Key Differences
| Aspect | LOLP | EENS |
|---|---|---|
| What it measures | Probability/frequency of shortage | Magnitude (energy) of shortage |
| Sensitivity to outage size | Insensitive — a 1 MW and 500 MW shortfall count equally | Sensitive — larger shortfalls give larger EENS |
| Customer impact | Indicates risk of load shedding | Indicates severity / duration of load shedding |
| Use | Planning criterion (reliability standard) | Economic evaluation (cost of unserved energy) |
5. Role in Reliability Evaluation
- Generation planning: LOLP is used to decide the reserve margin and the timing/size of new units. A typical NEA-type criterion is LOLP ≤ 0.1 day/year.
- Economic optimisation: EENS is multiplied by the Value of Lost Load (VOLL) to obtain the Expected Interruption Cost (ECOST): This allows comparison of the cost of adding a new plant against the benefit of reduced unserved energy.
- System expansion studies: Both indices are computed for each candidate expansion plan; the plan that meets the LOLP standard at minimum total cost (investment + ECOST) is selected.
- Operational use: EENS supports decisions on unit commitment, spinning reserve, and load shedding priorities during peak or outage conditions.
- Nepal-specific relevance: With a hydro-dominated system, seasonal river-flow variation and dry-season capacity shortage make EENS a particularly meaningful index for NEA's annual load-shedding assessment.
6. Limitations
- Both indices require accurate FOR data and load forecast; errors propagate directly.
- LOLP ignores the depth of the shortage; EENS ignores the frequency.
- Neither captures transmission constraints — these belong to composite/system reliability evaluation.
- They are expected values and do not indicate the worst-case scenario.
7. Conclusion
LOLP and EENS are complementary probabilistic indices for generation adequacy. LOLP serves as the planning standard (risk of shortage), while EENS quantifies the consequence (energy shortfall) and enables economic appraisal through ECOST. Together they provide a rational basis for capacity addition, reserve planning, and reliability-cost trade-off decisions in a power system such as Nepal's.
Answer checked by Claude Haiku · Oct 21, 2026